压缩空气泡沫灭浮顶罐密封圈火灾性能研究

杨震铭,陈涛,胡成,包志明   

  1. 应急管理部天津消防研究所,天津 300381
  • 出版日期:2020-05-15 发布日期:2020-05-15
  • 作者简介:杨震铭(1963-),男,应急管理部天津消防研究所副所长,研究员,主要从事消防科研管理和灭火技术研究,天津市南开区卫津南路110号,300381。
  • 基金资助:
    国家重点研发计划资助项目(2017YFC0806600);国家电网公司科技重大专项(52120518002L);应急管理部消防救援局科研计划项目(2019XFCX37);应急管理部天津消防研究所基科费项目(2019SJ14)

A study of fire extinguishing performance of compressed air foam on rim seal fire for floating roof tanks

YANG Zhen-ming, CHEN Tao, HU Cheng, BAO Zhi-ming   

  1. Tianjin Fire Research Institute of MEM,Tianjin 300381,China
  • Online:2020-05-15 Published:2020-05-15

摘要: 为了评估压缩空气泡沫系统用于浮顶罐的技术可行性,通过足尺灭火试验,研究不同供给强度和不同气液比下压缩空气泡沫对浮顶罐密封圈火灾的灭火性能,提出适宜的灭火应用参数。结果表明:在泡沫溶液供给强度为3.4 ~8.0 L/(min·m2)条件下,采用罐壁式压缩空气泡沫释放装置可以快速有效扑灭浮顶罐密封圈火灾,且不发生复燃;泡沫溶液供给强度越大,控灭火速度越快;气液比在8:1~12:1时对控灭火速度略有影响。建议实际工程中泡沫溶液供给强度不低于5 L/(min·m2),气液比不低于8:1,持续供泡时间不低于15 min。

关键词: 浮顶罐, 密封圈火灾, 压缩空气泡沫, 灭火性能, 泡沫灭火系统

Abstract:  In order to evaluate the technical feasibility of compressed air foam system for the rim seal fire of floating roof tanks, a series of full-scale fire extinguishing tests under different foam solution foam application rates and gas-liquid ratios were conducted to investigate the fire extinguishing performance of compressed air foam, and the suitable fire extinguishing application parameters were put forward.The results indicate that the rim seal fire for floating roof tanks was extinguished quickly and effectively by the rim seal discharge device of compressed air foam under the condition of the foam solution foam application rate being 3.4~8.0 L/(min·m2), and there was no re-ignition; the higher the foam solution foam application rateis, the faster the control and extinguishing speed is; the air/foam solution volume ratio has a slight effect on the fire control and extinguishing speed in the range of 8∶1 ~ 12∶1. It is suggested that the foam solution foam application rate is not less than 5 L/ (min·m2), the air/foam solution volume ratio is not less than 8∶1, and the apply duration of compressed air foam is no less than 15min in practical engineering.

Key words: floating roof tanks, rim seal fire, compressed air foam, fire extinguishing performance; foam extinguishing system