狭长空间内倾斜双电缆火蔓延行为试验研究

刘梦镇, 陈元, 赵胜中, 庄兆意   

  1. (山东建筑大学 热能工程学院,山东 济南 250101)
  • 收稿日期:2024-05-30 修回日期:2024-11-28 出版日期:2025-06-24 发布日期:2025-06-15
  • 作者简介:刘梦镇,山东建筑大学热能工程学院硕士研究生,主要从事地下建筑火灾研究,山东省济南市凤鸣路1000号,250101。
  • 基金资助:
    国家自然科学基金项目(52208115);山东省高等学校青创科技支持计划(2023KJ122);济南市科研带头人工作室项目(202333050)

Experimental study on fire spread behavior of inclined

Liu Mengzhen, Chen Yuan, Zhao Shengzhong, Zhuang Zhaoyi   

  1. (School of Thermal Engineering, Shandong Jianzhu University, Jinan Shandong 250101, China)
  • Received:2024-05-30 Revised:2024-11-28 Online:2025-06-24 Published:2025-06-15

摘要: 采用理论分析和燃烧试验相结合的方法,研究了不同倾斜角度和电缆间距对平行双电缆火蔓延行为的影响,重点关注了火焰形态、质量损失速率及火蔓延速率的变化规律。结果表明:电缆间距相同时,火焰高度、质量损失速率及火蔓延速率均随倾斜角度的增大而增大;倾斜角度相同时,火焰高度、质量损失速率及火蔓延速率均随电缆间距的增大先增加后减小,且均在间距为1倍电缆直径时达到最大值;电缆燃烧时,质量损失曲线不光滑,多处出现炭化层脱落导致的“台阶”式突变现象;燃烧过程中炭化层开始脱落的时刻大多集中在点燃电缆后200~400 s,炭化层的脱落现象均具有较强的随机性;倾斜角度相同时,燃烧相同长度的电缆,总损失质量不相同,0间距工况质量损失总是最少的;建立了平行双电缆在水平及倾斜条件下火蔓延速率预测公式,能够较好地预测火蔓延速率和倾斜角度和电缆间距之间的关系。

关键词: 平行双电缆, 倾斜角度, 电缆间距, 传热, 火蔓延

Abstract: This study investigates the effects of inclined angles and cable spacing on fire spread behavior of parallel dual cables through theoretical analysis and combustion experiments, with particular focus on flame morphology, mass loss rate, and fire spread rate. The results reveal that under constant cable spacing, the flame height, mass loss rate, and fire spread rate increase with greater inclined angles. At fixed inclined angles, these three parameters initially increase then decrease with expanding cable spacing, peaking when the spacing equals 1 times the cable diameter. During combustion, the mass loss curve exhibits irregular step-like abrupt changes caused by periodic detachment of carbonized layers. The initial detachment of carbonized layers predominantly occurs 200~400 s post-ignition, demonstrating significant temporal randomness. For cables of identical length burned at the same inclination, the zero-spacing configuration yields the minimum total mass loss. A predictive model for fire spread rate under horizontal and inclined conditions was developed, effectively correlating the spread rate with both inclination angle and cable spacing.

Key words: parallel dual cables, inclined angle, cable spacing, heat transfer, fire spread