主管:中华人民共和国应急管理部
主办:应急管理部天津消防研究所
ISSN 1009-0029  CN 12-1311/TU

消防科学与技术 ›› 2025, Vol. 44 ›› Issue (8): 1092-1096.

• • 上一篇    下一篇

乡村小学宿舍火灾试验研究

梁志宏1, 单威威2, 张文龙2   

  1. (1.河南省消防救援总队,河南 郑州 450000; 2.河南理工大学,河南 焦作 454000)
  • 收稿日期:2024-12-06 修回日期:2025-06-19 出版日期:2025-08-15 发布日期:2025-08-15
  • 作者简介:梁志宏,男,河南省消防救援总队高级专业技术职务,一级指挥长消防救援衔,主要从事火灾事故调查工作,河南省郑州市文苑南路38号,450000,gaxf@sohu.com。

Experimental study on dormitory fire in rural primary schools

Liang Zhihong1, Shan Weiwei2, Zhang Wenlong2   

  1. (1. Henan Fire and Rescue Brigade, Zhengzhou Henan 450000, China; 2. Henan Polytechnic University, Jiaozuo Henan 454000, China)
  • Received:2024-12-06 Revised:2025-06-19 Online:2025-08-15 Published:2025-08-15

摘要: 为了研究乡村小学宿舍火灾防控问题,采用全尺寸火灾试验方法,系统模拟了不同起火条件下的火灾发展过程。基于全尺寸小荷载下铺起火、小荷载上铺起火以及大荷载上铺起火3种场景,通过布置温度和烟气采集系统,实时监测火灾发生与蔓延过程中的温度及烟气扩散特性。结果表明,当下铺作为起火点时,火焰会迅速蔓延至整个下铺区域并形成立体火灾,最终引发猛烈燃烧;而上铺起火初期燃烧相对缓慢,但随着火势发展同样会导致猛烈燃烧。基于试验结果,提出了加强消防安全教育、增设自动报警系统和优化安全疏散设施等预防对策,旨在为乡村小学校舍火灾防控提供科学试验数据和技术支持。

关键词: 乡村小学宿舍, 全尺寸火灾试验, 火灾防控措施

Abstract: In order to study the fire prevention and control of rural primary school dormitory, the full-scale fire test method was used to systematically simulate the fire development process under different fire conditions. Based on the three scenarios of full-scale small-load lower bunk fire,full-scale small-load upper bunk fire and large-load upper bunk fire, the temperature and smoke collection system is arranged to monitor the temperature and smoke diffusion characteristics in the process of fire occurrence and spread in real time. The results show that when the lower bunk is used as the ignition point, the flame will quickly spread to the whole lower bunk area and form a three-dimensional fire, which will eventually lead to violent combustion; The upper bunk fire burns relatively slowly at the initial stage of fire, but it will also cause violent combustion as the fire develops. Based on the test results, the prevention countermeasures such as strengthening fire safety education, adding automatic alarm system and optimizing safety evacuation facilities were put forward, aiming to provide scientific test data and technical support for the fire prevention and control of rural primary school buildings.

Key words: rural primary school dormitory, full-scale fire experiment, fire prevention measures