消防科学与技术 ›› 2022, Vol. 41 ›› Issue (1): 142-145.

• • 上一篇    

护套线过电流诱发短路故障起火过程及痕迹特征

余 韬1,刘义祥2,李 阳2,高 阳2   

  1. (1.中国人民警察大学 研究生院,河北 廊坊065000;2.中国人民警察大学 物证鉴定中心,河北 廊坊 065000)
  • 出版日期:2022-01-15 发布日期:2022-01-15
  • 作者简介:余 韬(1997-),男,江西九江人,中国人民警察大学硕士研究生,主要从事电气火灾调查相关领域的研究,河北省廊坊市安次区西昌路220号,065000。

The process and trace of cables breakdown induced by overcurrent.

YU Tao1, LIU Yi-xiang2, LI Yang2,GAO Yang2   

  1. (1. Graduate School, China People's Police University, Heibei Langfang 065000, China; 2. Institute of Forensic Science, China People's Police University, Heibei Langfang 065000, China)
  • Online:2022-01-15 Published:2022-01-15

关键词: RVVB护套线;过电流;短路故障;起火过程

Abstract: In order to study the fire risk of short-circuit fault caused by overcurrent of electric RVVB wire, this paper built a test platform for RVVB wire overcurrent induced short-circuit faults, and studied the fire process and trace of short circuit fault. The initial short circuit occurrence time, combustion characteristics and trace characteristics when the RVVB wire was short-circuited were studied. The results showed that when I≥ 45 A, the RVVB wire will appear short circuit breakdown phenomenon and cause open fire combustion; When I= 66 A, the average time of short-circuit fault induced by over-current is shortened from 1 803.4 s of I=45 A to 52.8 s, and the combustion time of open fire fluctuates from 16.4 s to 28.96 s, which increases the fire risk; The short-circuit fault induced by overcurrent in the RVVB wire will produce arc fusion marks such as sphere shape, semicircle shape, pointed shape, joint shape, pit shape, fracture shape,and overlapping shape, as well as splashing fusion marks with different diameters.The research results can provide a theoretical basis for the ignition mechanism of short circuit fault induced by over-current and the identification of weld marks.

Key words: RVVB wire; overcurrent; short circuit fault; a fire process