主管:中华人民共和国应急管理部
主办:应急管理部天津消防研究所
ISSN 1009-0029  CN 12-1311/TU

消防科学与技术 ›› 2025, Vol. 44 ›› Issue (5): 585-589.

• •    下一篇

基于浸没技术的锂电池模组热失控抑制研究

许晓元1,2, 张少禹1,2, 卓萍1,2, 储玉喜1,2   

  1. (1.应急管理部天津消防研究所,天津 300381; 2.电化学能源消防安全联合创新应急管理部重点实验室,天津 300381)
  • 收稿日期:2024-07-15 修回日期:2024-08-19 出版日期:2025-05-15 发布日期:2025-05-15
  • 作者简介:许晓元,应急管理部天津消防研究所副研究员,博士,主要从事锂电池和石油化工火灾防控技术研究,天津市南开区卫津南路110号,300381。
  • 基金资助:
    国家重点研发计划项目“国际锂离子电池储能安全评价关键技术合作研发”(2022YFE0207400)

Research on the suppression of thermal runaway of lithium battery modules based on immersion technology

Xu Xiaoyuan1,2, Zhang Shaoyu1,2, Zhuo Ping1,2, Chu Yuxi1,2   

  1. (1. Tianjin Fire Science and Technology Research Institute of MEM, Tianjin 300381, China; 2. Key Laboratory of Electrochemical Energy Safety Ministry of Emergency Management, Tianjin 300381, China)
  • Received:2024-07-15 Revised:2024-08-19 Online:2025-05-15 Published:2025-05-15

摘要: 电池热失控风险已经成为制约新能源行业发展的瓶颈问题。针对电池热失控应急处置难题,开发了电池模组热失控浸没抑制试验平台,开展了不同注入策略下电池热失控试验,研究了浸没液对延缓电池热失控和防止电池热失控的有效性。结果表明,当电池热失控后,在浸没液40 s注满模组箱的前提下,可抑制电池温升,最大降温速率可达78.7 ℃/s;当电池开阀后,在浸没液40 s注满模组箱的前提下,最大降温速率可达17.9 ℃/s,可防止热失控发生。

关键词: 锂电池, 热失控, 浸没, 冷却, 温度, 抑制

Abstract: The risk of battery thermal runaway has become a bottleneck problem restricting the development of the new energy industry. In response to the emergency response problem of battery thermal runaway, this paper developed a battery module thermal runaway immersion suppression experimental platform, conducted battery thermal runaway experiments under different injection strategies, and studied the effectiveness of immersion liquid in delaying battery thermal runaway and preventing battery thermal runaway. The results showed that when the battery thermal runaway occurred, the disposal condition of filling the module box with immersion solution within 40 seconds could suppress the temperature rise of the battery, with a maximum cooling rate of 78.7 ℃/s; When the battery valve is opened and the immersion liquid is filled into the module box within 40 seconds, the maximum cooling rate can reach 17.9 ℃/s to prevent thermal runaway.