水幕封堵系统在半封闭隧道中自熄灭火关键参数研究

王凌翔, 张继鹤, 戴政, 陈孜忻, 余龙星   

  1. (福州大学 环境与安全工程学院,福建 福州 350116)
  • 收稿日期:2024-11-11 修回日期:2025-04-22 出版日期:2025-12-15 发布日期:2025-12-25
  • 作者简介:王凌翔,福州大学环境与安全工程学院硕士研究生,主要从事受限空间火灾烟气控制及灭火技术研究,福建省福州市闽侯县学园路2号,350116。
  • 基金资助:
    国家自然科学基金(52574232);国家自然科学基金(52211530486);福建省自然科学基金(2023J05104)

Study on key parameters of self-extinguishing fire in semi-enclosed tunnels using water curtain blocking system

Wang Lingxiang, Zhang Jihe, Dai Zheng, Chen Zixin, Yu Longxing   

  1. (College of Environment and Safety Engineering, Fuzhou University, Fuzhou Fujian 350116, China)
  • Received:2024-11-11 Revised:2025-04-22 Online:2025-12-15 Published:2025-12-25

摘要: 本文通过数值模拟方法,系统研究了水幕封堵对一端封闭隧道火灾的自熄灭效果。为评估不同水幕参数对火灾自熄灭的影响,基于耗氧法提出了量化自熄效果的系数Kw,定义为理论熄灭时间与实际熄灭时间的比值。结果表明:粒径在200~400 μm下对Kw影响并不显著,但在300 μm表现出相对较高的自熄效果;相较于完全封闭(隔墙封堵)的情况,水幕封堵在高火源功率下(10~30 MW)能促进火灾的自熄灭,而在低火源功率下(5 MW)则可能产生一定的抑制效果;在粒径为300 μm的条件下,随着喷淋压力从0.01 MPa提升至0.40 MPa,Kw呈现出先上升后趋于稳定的趋势。当喷淋压力达到一定阈值时,继续提高压力对自熄灭的影响减小,但对于顶棚温度的热衰减方面,则表现出显著的正向作用;在能够实现自熄灭的情况下,若继续增加水幕排数,反而可能导致下降,尽管增加排数能够提高水幕对高温烟气的热衰减能力,但提升幅度相对有限。

关键词: 单侧封闭隧道, 水幕, 自熄灭, 耗氧法, FDS

Abstract: This paper systematically investigates the self-extinguishing effects of water curtain blockades in fires within semi-enclosed tunnel using numerical simulation methods. To evaluate the impact of different water curtain parameters on fire self-extinction, a coefficient Kw was proposed based on the oxygen consumption method, defined as the ratio of theoretical extinguishing time to actual extinguishing time. The results show that particle size does not significantly affect Kw within the droplet size of 200~400 μm, but a relatively higher self-extinguishing effect is observed at 300 μm; Compared to complete enclosure (partition wall blockage), water curtain blockades promote fire self-extinction under high HRR (10~30 MW), while they may exert some inhibitory effects under low HRR (5 MW); With a particle size of 300 μm, as the spray pressure increases from 0.01 MPa to 0.40 MPa, Kw first rises and then stabilizes. When the spray pressure reaches a certain threshold, further increasing the pressure has a diminishing effect on self-extinguishment but significantly enhances the attenuation of ceiling temperature; In cases where self-extinction can be achieved, increasing the number of water curtain rows may lead to a decrease in , although additional rows enhance the thermal decay of high-temperature smoke, the improvement is relatively limited.