消防科学与技术 ›› 2026, Vol. 45 ›› Issue (2): 86-92.

• • 上一篇    下一篇

喷嘴结构对惰性气体灭火剂喷射噪声的影响研究

张德华1,2,3, 李兆宇1,2,3, 徐儒1,2,3, 刘连喜1,2,3   

  1. (1.应急管理部天津消防研究所, 天津300381; 2.工业与公共建筑火灾防控技术应急管理部重点实验室,天津 300381; 3.天津市消防安全技术重点实验室,天津 300381)
  • 收稿日期:2024-12-10 修回日期:2025-04-18 出版日期:2026-02-11 发布日期:2026-02-15
  • 作者简介:张德华,应急管理部天津消防研究所第一检测部,硕士,主要从事固定灭火系统的检验检测工作,天津市南开区卫津南路110号,300381,272734296@qq.com。
  • 基金资助:
    应急管理部天津消防研究所基科费项目(2024SJ08)

Research on the influence of nozzle structure on the injection noise of inert gas fire extinguishing agents

Zhang Dehua1,2,3, Li Zhaoyu1,2,3, Xu Ru1,2,3, Liu Lianxi1,2,3   

  1. (1. Tianjin Fire Science and Technology Research Institute of MEM, Tianjin 300381, China; 2. Tianjin University,Tianjin 300072, China)
  • Received:2024-12-10 Revised:2025-04-18 Online:2026-02-11 Published:2026-02-15

摘要: 作为保护数据中心机房消防安全的惰性气体灭火系统,在火灾发生时,其喷嘴喷放高压惰性气体产生的高强度噪声,会对机房内大量的机械硬盘造成不可逆的损伤。本文研究了现有惰性气体喷嘴在喷放过程中的总体噪声强度(Z加权)及其在不同频率段的噪音强度分布,发现噪声的产生主要与喷嘴喷孔处气体的相对流速及流动状态有关。通过试验验证了为喷嘴加装疏松多孔的外罩可有效降低喷放噪声,且通过优化外罩形状可进一步抑制高频段的喷放噪声。最终实现了喷嘴末端压力在0~3 MPa范围内,全频段噪声分声压级均控制在100 dB以下,具有良好的降噪效果,有效保证了惰性气体灭火系统动作时数据中心机房内存储硬盘的安全性,具备良好的应用前景。

关键词: 数据中心机房, 气体灭火, 降噪喷嘴, 机械硬盘, 降噪性能

Abstract: As an inert gas fire extinguishing system for protecting the fire safety of engine room of data centers, the high-intensity noise generated by the high-pressure inert gas sprayed from its nozzle during a fire can cause irreversible damage to a large number of mechanical hard drives in the data center. This article studies the overall noise intensity (Z-weighted) of existing inert gas nozzles during the spraying process and their noise intensity distribution in different frequency ranges. It is found that the generation of noise is mainly related to the relative flow velocity and flow state of the gas at the nozzle orifice. It has been verified through experiments that adding a loose and porous outer cover to the nozzle can effectively reduce spray noise, and optimizing the shape of the outer cover can further suppress high-frequency spray noise. Finally, the nozzle end pressure was achieved within the range of 0 MPa to 3 MPa, and the full frequency noise level was controlled below 100 dB, with good noise reduction effect, effectively ensuring the safety of the storage hard disk in the data center room during the operation of the inert gas fire extinguishing system, and having good application prospects.

Key words: data center engine room, gas fire suppression, noise-reducing nozzle, hard disk drive (HDD), noise reduction performance