陶坛酒库火灾后事故排风系统设计探讨

钟正强1, 常凡仲1, 明星1, 郑斌2, 时训先3, 范韬3   

  1. (1.贵州茅台酒股份有限公司,贵州 遵义 564500; 2.中国消防救援学院,北京 102202; 3.中国安全生产科学研究院,北京 100012)
  • 收稿日期:2024-10-11 修回日期:2025-01-25 出版日期:2025-05-15 发布日期:2025-05-15
  • 作者简介:钟正强,贵州茅台酒股份有限公司党委委员、副总经理,主要从事酒类企业生产技术与管理方面的工作,贵州省仁怀市茅台镇贵州茅台酒股份有限公司办公大楼,564500。
  • 基金资助:
    白酒陶坛贮存酒库火灾特性与惰性气体(二氧化碳)灭火技术装备研究项目资助(MTGF2023008)

Discussion on the design of exhaust system for accidents after a fire in taotan wine warehouse

ZhongZhengqiang1, Chang Fanzhong1, Ming Xing1, Zheng Bin2, Shi Xunxian3, Fan Tao3   

  1. (1. Kweichow Moutai Co., Ltd., Zunyi Guizhou 564500, China; 2. China Fire and Rescue Institute, Beijing 102202, China; 3. China Academy of Safety Production Science, Beijing 100012, China)
  • Received:2024-10-11 Revised:2025-01-25 Online:2025-05-15 Published:2025-05-15

摘要: 为了研究采用二氧化碳灭火系统时陶坛酒库火灾后事故排风系统的设计参数,依照现行规范的要求,计算了某陶坛酒库采用二氧化碳系统灭火后排风系统的通风换气次数、环境风速和排风口参数,利用PHAST软件计算了在3种模拟工况下,二氧化碳排放后在下风方向的气体体积分数分布范围。结果表明,当酒库的换气次数为12次/h时,建议排风口的风速为14.0 m/s,排风口面积为0.13 m2,且排风口应设置在距离地面高度2.1 m以上,并与重点场所的最小距离不小于6.4 m。研究结果可为陶坛酒库采用二氧化碳灭火系统时的事故排风系统设计提供数据支撑,并为酒库火灾的灭火救援安全提供参考。

关键词: 酒库, 灭火, PHAST, 二氧化碳, 排风系统

Abstract: To study the design parameters of the exhaust air system for CO2 fire extinguishing in Taotan wine warehouse, according to the current national standards, the ventilation frequency, environmental wind speed, and exhaust parameters of the exhaust system after carbon dioxide fire extinguishing in a certain pottery wine cellar were calculated. The gas volume fraction distribution in the downwind direction after carbon dioxide emission was calculated using PHSAT software under three simulated operating conditions. According to the calculation results, when the air exchange rate of the wine cellar is 12 times/h, it is recommended that the wind speed of the exhaust outlet be 14.0 m/s, the exhaust outlet area be 0.13 m2, and the height of the exhaust outlet should be set at a distance of 2.1 m or more from the ground, with a minimum distance of not less than 6.4 m from key areas. The research results can provide effective data support for the design of exhaust systems after carbon dioxide fire extinguishing in wine warehouses, and provide reference for the rescue of wine warehouse fires.

Key words: wine cellar, fire extinguishing, PHAST, carbon dioxide, exhaust system