Fire Science and Technology ›› 2021, Vol. 40 ›› Issue (1): 51-54.
Previous Articles Next Articles
YAN Ming-qiang, LI Li-jun, ZHANG Ze-jiang
Online:
Published:
Abstract: In this paper, a large-scale fire test of ETFE film was designed, the combustion characteristics of ETFE film under a fire with a heat release rate of 4 MW were studied, and whether the ETFE film burns with droplets under standard test and largescale fire test conditions was discussed. The results showed that with the heat release rate of 4 MW, the ETFE film where the flame can reach has softened, burned through and dripped, and where the flame can't reach has maintained integrity. The ETFE film that meets the B1 (d0) level requirements specified in GB 8624-2012 is likely to show droplets in actual fires, and whether ETFE film will drip in actual fires shall not only depend on the results of standard tests. Whether the burning of ETFE film will cause droplets is related to the size of the film, installation method and fire conditions, etc.
Key words: ETFE film, roofing material, fire test, droplet
YAN Ming-qiang, LI Li-jun, ZHANG Ze-jiang. Large-scale fire test of ETFE film roofing material[J]. Fire Science and Technology, 2021, 40(1): 51-54.
0 / / Recommend
Add to citation manager EndNote|Ris|BibTeX
URL: https://www.xfkj.com.cn/EN/
https://www.xfkj.com.cn/EN/Y2021/V40/I1/51
Design and experimental verification of aspirating smoke detection and alarm system for ship cabin