主管:中华人民共和国应急管理部
主办:应急管理部天津消防研究所
ISSN 1009-0029  CN 12-1311/TU

Fire Science and Technology ›› 2023, Vol. 42 ›› Issue (1): 47-50.

Previous Articles     Next Articles

Study on the influence of distance between two fire sources and aspect ratio on ground temperature profile

Zhou Jin
  

  1. (Shaoyang Fire and Rescue Division, Hunan Shaoyang 422000, China)
  • Online:2023-01-15 Published:2023-01-15

Abstract:

The influence of distance between two fire sources, aspect ratios and hear release rates on the temperature distribution on the centerline of the two fire sources were experimentally studied. Propane burners were used to simulate the fire sources. The distances between two fire sources were 0.2 m, 0.4 m and 0.6 m, and the aspect ratio of fire sources were 1, 3 and 6. The results show that the longitudinal temperature profile on the ground centerline induced by two fire sources decreases exponentially. When other conditions are the same, with the increase of distance of fire sources, the temperature at the same position on the centerline near the fire source decreases gradually, while the temperature at the same position on far field of fire source is basically unchanged. The effect of aspect ratio of fire source on the temperature on the centerline of two fire sources is not monotonous. Based on the dimensional analysis method, an empirical correlation on the centerline temperature profile which relates to fire source spacing, aspect ratio and heat release rate is established. Predictions the proposed correlation agree reasonably with experimental data.

Key words: