Fire Science and Technology ›› 2023, Vol. 42 ›› Issue (10): 1393-1397.

Previous Articles     Next Articles

Effectiveness of compressed air foam nozzle for extinguishing 20A wood crib fire in super high⁃rise building

Chen Tao1,2,3, Wang Yuwei1,2,3, Zhang Peng1,2,3, Qin Guoyang1,2,3   

  1. (1. Tianjin Fire Science and Technology Research Institute of MEM, Tianjin 300381, China; 2. Key Laboratory of Fire Protection Technology for Industry and Building, Ministry of Emergency Management, Tianjin 300381, China; 3. Tianjin Key Laboratory of Fire Safety Technology, Tianjin 300381, China)
  • Online:2023-10-15 Published:2023-10-15

Abstract: Compressed air foam fire extinguishing technology is an important development direction to solve the fire fighting problem in super high-rise buildings, but the fire extinguishing performance of compressed air foam after vertical long-distance transport is still to be further studied. In this paper, the foam nozzle actually configured in the super high-rise buildings was used to simulate the equivalent foam with the same performance as the actual working condition by adjusting the input parameters. And the ability of compressed air foam after vertical long-distance transport to extinguish Class A fire was verified by the standard 20A wood crib fire extinguishing test. The results showed that the flame can be completely extinguished for 141 s when the mixed liquid is 92 L/min and the gas-liquid ratio of the foam is 9.8:1.0, and there was no reignition within 10 min. Meanwhile, the flame can be completely extinguished for 54 s when the mixed liquid is 126 L/min and the gas?liquid ratio of the foam is 6.0:1.0, and there was no reignition within 10 min.

Key words: super high-rise building, compressed air foam, foam nozzle, equivalent foam, 20A wood crib fire