主管:中华人民共和国应急管理部
主办:应急管理部天津消防研究所
ISSN 1009-0029  CN 12-1311/TU

Fire Science and Technology ›› 2023, Vol. 42 ›› Issue (2): 149-152.

    Next Articles

Experimental study on wood crib fire with modified dry water extinguishing agent

Zhu Guoqing1,2,3, Chen Chunna1,2,3, Wang Yang1,2,3,Liu Chunxiao1,2,3   

  1. (1. Jiangsu Key Laboratory of Fire Safety in Urban Underground Space, China University of Mining and Technology, Jiangsu Xuzhou 221116, China; 2. School of Safety Engineering, China University of Mining and Technology, Jiangsu Xuzhou 221116, China; 3. Public Safety and Fire Research Institute, China University of Mining and Technology, Jiangsu Xuzhou 221116, China)
  • Online:2023-02-15 Published:2023-02-15

Abstract: The new-type dry water fire extinguishing agent has a good fire extinguishing effect due to its high water content and special core-shell structure. In order to explore the fire extinguishing effect of dry water on wood crib fires, the modified dry water was prepared by adding ammonium dihydrogen phosphate and carried out small-scale wood crib fire extinguishing experiments. The results show that the dry water fire extinguishing agent can extinguish the fire without re-ignition, the fire control time of the modified dry water is only 8 s, and the flame height continues to drop rapidly during the fire control process, while the fire control time of the dry powder is 20 s, and re-ignition occurred 39 s after spraying. The temperature suppression effect of the modified dry water on the flame area and the wood crib was better than that of the dry powder. The average temperature drop rate is as high as 17.00 ℃/s, which is 1.94 times the average temperature drop rate under the action of dry powderduring fire control time. The modified dry water can effectively reduce the internal temperature of the wood crib, the average temperature drop rate in the center of the wood crib is 8.78 ℃/s during within 50 s of spraying, while the dry powder lacks cooling effect, and the average temperature drop rate in the center of the wood crib is only 6.10 ℃/s, which cannot effectively suppress smoldering.

Key words: modified dry water, fire extinguishing agent, wood crib fire, fire control time, average temperature drop rate