主管:中华人民共和国应急管理部
主办:应急管理部天津消防研究所
ISSN 1009-0029  CN 12-1311/TU

Fire Science and Technology ›› 2023, Vol. 42 ›› Issue (3): 367-369.

Previous Articles     Next Articles

Reliability analysis of automatic start-up of fire pump of wet automatic water-spray fire-extinguishing system

Li Nianci1, Wang Yu2, Zhou Mingtan3   

  1. (1. Zhejiang Fangyuan An Fire Technology Research Institute, Zhejiang Hangzhou 310053, China; 2. Zhejiang Contemporary Architectural Design & Research Institute,Zhejiang Hangzhou 310012, China; 3. Zhejiang Fangyuan An Fire Technology Co., Ltd., Zhejiang Hangzhou 310053, China)
  • Online:2023-03-15 Published:2023-03-15

Abstract: Abstract: The reliability and existing risks of the three automatic starting devices of the automatic sprinkler system are analyzed in detail. In view of the conflict between Article 11.0.1 of GB 50084-2017 Code for design of automatic sprinkler systems and other standards, and the problems in the reliability and safety of the automatic sprinkler system, the paper proposes that: for the wet automatic sprinkler systems, the pressure switch on the alarm pipeline of the alarm valve group directly starts the fire pump, which is the optimal configuration of the system and meets the requirements of timely startup and safe fire extinguishing of the wet system.

Key words: Key words: automatic sprinkler system, fire pump, pressure switch, flow switch