主管:中华人民共和国应急管理部
主办:应急管理部天津消防研究所
ISSN 1009-0029  CN 12-1311/TU

Fire Science and Technology ›› 2026, Vol. 45 ›› Issue (3): 109-114.

Previous Articles     Next Articles

Experimental study on extinguishing silicon mud stack with water based extinguishing agent

Zhang Xianzhong1,2,3, Zhang Guosheng4, Ke Xin1,2,3, Hu Cheng1,2,3   

  1. (1. Tianjin Fire Science and Technology Research Institute of MEM, Tianjin 300381, China; 2. Key Laboratory of Fire Protection Technology for Industry and Public Building, Ministry of Emergency Management, Tianjin 300381, China; 3. Tianjin Key Laboratory of Fire Safety Technology, Tianjin 300381, China; 4. Baotou Fire and Rescue Division, Baotou Inner Mongolia 014000, China)
  • Received:2024-12-31 Revised:2025-05-07 Online:2026-03-15 Published:2026-03-15

Abstract: To address the frequent fires in the transportation and storage of silica mud in recent years, and the lack of effective fire extinguishing methods, this study employed a laboratory-level silica mud stack fire extinguishing test model to evaluate the feasibility of using water to extinguish silica mud stack fires, investigate the effects of extinguishing water with different pH values on the fire-fighting efficiency of silica mud stack fires, and compare the effects of water and foam extinguishing agents on silica mud stack fire-fighting effectiveness. The results show that it is technically feasible to use acidic and neutral water to extinguish silica mud stack fires, while using alkaline water to extinguish fires will lead to a sharp increase in the stack fire, which poses high risk; the lower the pH value of the fire extinguishing water, the better the cooling and fire extinguishing effects; AFFF foam has a good cooling and fire extinguishing effect on the surface of the stack, but has a poor cooling effect on the inside of the stack.

Key words: silicon mud, stack fire, pH, aqueous film-forming foam